Type Code CTI 100 , Weight 1.8 Kg , Approval C UL US, CE, EAC More detailsThe CTI product range is modular, flexible and offers a large selection of clip-on auxiliary functions and accessories: Aux. contacts, alarm contacts, voltage- and undervoltage trips. Compact design DIN rail mounting Motor application Short-circuit protection Overload protection of motors (31.5 - 45 kW) Setting range: 40 - 90A Operation switch (manual motor starter) Isolation switch (with locking device) Emergency switch (with undervoltage trip) Indications: Test and reset functions ON or OFF Thermal and electromagnetic trip
Type Code | CTI 100 |
Weight | 1.8 Kg |
Approval | C UL US, CE, EAC |
Breaking cap. Ics, 380-415 V | 25 kA |
Current range | 63,00 - 90,00 A |
EAN no. | 5702423074280 |
Function | Overload and short-c. protect |
Max. load, AC-3 [kW] | 45,00 kW |
Max. trip current | 1.260,0 A |
Descript. | CIRCUIT BREAKER |
Prod. Group | Contactors and motor starters |
Prod. name | CIRCUIT BREAKER |
UL approval file | E148460 |
Used for | MOTORS |